Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T05CM04503
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/13/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t05cm04503 6/13/06 1. Keynote 25 indicates a 5.6 KW load on Ckts D-14,16 and D-16,18. These circuits only are load to 3 KW on the panel schedule. This would make for a 14.4A circuit, whereas according to the keynote this is a 25A circuit, in which case the 20A CB is not sufficient. Please clarify. 2. Modify all load calculations as necessary per Comment #1 above. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/05/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |