Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T05CM04503
Review Name: REVISION - - 2ND
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM04503 5/11/03 1. Eliminate the redundant ground between the new disconnect and the existing gutter. Reference NEC 250.24 (B). 2. New circuit configuration according to panel schedules does not reflect layout on plans. 3. Modify the Load Calculations Summary according to the new panel loading as necessary. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/13/2006 | ADRIANNE OLIVO | OUT TO CUSTOMER | Completed |