Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM04502
Parcel: 11307145A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04502
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/30/2005 JIM EGAN FIRE REVIEW Approved
08/30/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide complete water pressure calculations.
2. Revise the fixture units for the new fixtures per Tables 6-3 and 7-3, UPC 1994. Include the ice machine in the calculations.
3. Justify using an indirect connection for the 2-compartment sink.
08/30/2005 DAVID RIVERA ZONING REVIEW Approved
08/30/2005 ROBERT SHERRY WATER REVIEW Approved
08/30/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide the refrigerating capacities for the walk-in coolers.
2. Provide the sizes of the condensate drains for the two walkin coolers.
3. Provide the refrigerating capacity and state whether condensate drains are required for the new refrigerated produce display case.
08/31/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE ACCESSIBILE RESTROOM FOR EACH SEX SEE SECTION 2902.2.
08/31/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t05cm04502

1. Please demonstrate that no phase of Panel T4 is overloaded.
2. Provide feeder size for Panel T4.
09/09/2005 JMORALE1 WWM REVIEW Needs Review
09/09/2005 JMORALE1 ENGINEERING REVIEW Needs Review