Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04502
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/30/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
08/30/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide complete water pressure calculations. 2. Revise the fixture units for the new fixtures per Tables 6-3 and 7-3, UPC 1994. Include the ice machine in the calculations. 3. Justify using an indirect connection for the 2-compartment sink. |
08/30/2005 | DAVID RIVERA | ZONING | REVIEW | Approved | |
08/30/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/30/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the refrigerating capacities for the walk-in coolers. 2. Provide the sizes of the condensate drains for the two walkin coolers. 3. Provide the refrigerating capacity and state whether condensate drains are required for the new refrigerated produce display case. |
08/31/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) PROVIDE ACCESSIBILE RESTROOM FOR EACH SEX SEE SECTION 2902.2. |
08/31/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | t05cm04502 1. Please demonstrate that no phase of Panel T4 is overloaded. 2. Provide feeder size for Panel T4. |
09/09/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
09/09/2005 | JMORALE1 | ENGINEERING | REVIEW | Needs Review |