Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM04485
Parcel: 10511043B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04485
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/29/2005 TERRY STEVENS ZONING REVIEW Approved
08/30/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/30/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04485 8/30/05

1. Provide available fault current at Panel IGP-ACC.
2. Clarify TEP service entrance capacity. TEP does not publish 1800A in SR-510. It shall be clear that the service is not overloaded.
08/30/2005 ROBERT SHERRY WATER REVIEW Approved
08/30/2005 JIM EGAN FIRE REVIEW Approved
08/30/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the design to a ducted return or comply with the requirements of Section 602, IMC 2000.
08/30/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved
08/31/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) PROVIDE BUILDING PLAN SHOWING ACCESSIBLE RESTROOMS AND CLARIFY DISTANCE TRAVELED. IT APPEARS WATER CLOSET IS NOT WHEEL CHAIR ACCESSIBLE.
2) DETAIL 1/T1-2.1 CLARIFY METAL STRAP FOR UNBRACED PARTITION ALTERNATES ATTACHMENT BY 90 DEGREES TO PROVIDE BRACING IN SEISMIC AND STRAPS NEED TO ATTACH TO METAL STUD NOT THE CEILING GRID. SEE SECTION 1621.1.2.
09/19/2005 KMEDINA1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2005 KMEDINA1 OUT TO CUSTOMER Completed