Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04478
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/30/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide calculations and a design for the water supply to the restroom. Reference Section 610.1, UPC 1994. 2. Revise the size of the trap and trap arm from the lavatory to a maximum of 1-1/2". Reference Table 7-3 footnote, UPC 1994. 3. Revise the length of the trap arm for the lavatory to a maximum of 3'-6" (for 1-1/2" trap arm). Reference Section 1002.2, UPC 1994. 4. Specify the fixtures and fittings to be installed. |
08/30/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/30/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide ventilation for the restroom that complies with the requirements of Section 403.3, IMC 2000. |
09/06/2005 | DROBEY1 | FIRE | REVIEW | Needs Review | |
09/06/2005 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/06/2005 | DROBEY1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
09/06/2005 | DROBEY1 | ZONING | REVIEW | Needs Review | |
09/06/2005 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
09/06/2005 | DROBEY1 | ENGINEERING | REVIEW | Needs Review |