Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 2ND
Permit Number - T05CM04478
Review Name: REVISION - - 2ND
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/23/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM04478 3/23/06 1. GND and bond for new transformer shall be sized per NEC Table 250.66. Please change #6 to 1/0. 2. If Water Heater is existing, please note it as such. Otherwise, provide Plumbing plans. 3. Please note that using the Bussman method for calculation the AFC on the secondary of a transformer, it is necessary to multiply the result by the Primary/Secondary ratio. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/24/2006 | JMORALE1 | OUT TO CUSTOMER | Completed |