Review Date Reviewer's Name Type of Review Description Status Comments
03/23/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM04478 3/23/06

1. GND and bond for new transformer shall be sized per NEC Table 250.66. Please change #6 to 1/0.
2. If Water Heater is existing, please note it as such. Otherwise, provide Plumbing plans.
3. Please note that using the Bussman method for calculation the AFC on the secondary of a transformer, it is necessary to multiply the result by the Primary/Secondary ratio.