Permit Number: T05CM04443
Parcel: 11005014C

Review Status: Completed

Review Details: REVISION - WALK THRU

Permit Number - T05CM04443
Review Name: REVISION - WALK THRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/11/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Gravity drainage required whenever practical. Reference Section 709.0, UPC 1994.
2. Sump pumps for public fixtures must have duplex pumps. Reference Section 710.9, UPC 1994.
11/09/2005 JMORALE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review