Permit Number: T05CM04419
Parcel: 107040140

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04419
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/25/2005 JIM EGAN FIRE REVIEW Approved
08/25/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/25/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied S1. CLARIFY ACCESSIBILITY.
S2. COMPLETE CODE REVIEW CHECKLIST.
S3. SHOW TYPE OF CONSTRUCTION AND OCCUPANCY OF ADJACENT TENANT ON DRAWINGS.
08/25/2005 ROBERT SHERRY WATER REVIEW Approved
08/25/2005 TERRY STEVENS ZONING REVIEW Approved
08/25/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the airflow quantities for all of the supply outlets for the revised systems.
2. Provide calculations to support the amount of outside air being provided for the revised systems.
3. State if the revised systems have or now require duct smoke detectors.
08/25/2005 CHRISTY FOREMAN ELECTRICAL-COMMERCIAL REVIEW Approved
08/25/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
08/26/2005 GERRY KOZIOL WWM REVIEW Approved