Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04419
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/25/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/25/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/25/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | S1. CLARIFY ACCESSIBILITY. S2. COMPLETE CODE REVIEW CHECKLIST. S3. SHOW TYPE OF CONSTRUCTION AND OCCUPANCY OF ADJACENT TENANT ON DRAWINGS. |
| 08/25/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/25/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 08/25/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show the airflow quantities for all of the supply outlets for the revised systems. 2. Provide calculations to support the amount of outside air being provided for the revised systems. 3. State if the revised systems have or now require duct smoke detectors. |
| 08/25/2005 | CHRISTY FOREMAN | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/25/2005 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
| 08/26/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |