Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T05CM04401
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/20/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reducing the flowrate of the supply air will not prevent recirculation of the air from the restroom if the exhaust fan is shut off with the local light switch. Reference Section 403.2.1, IMC 2000. |
| 10/20/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. This comment was addressed but the equipment schedule still calls for a remote chiller. Clarify the position of the remote chiller for the drinking fountain; In the Janitor's room or under the sink counter? Provide an installation detail to show that the unit is being installed per the product listing. Reference Section 301.1.1, UPC 1994. 2. This comment was addressed but the two-way cleanout depicted on the waste isometric (sheet P2.0) still appears to violate Section 707.6, UPC 1994, which requires each cleanout fitting to be installed in the direction of flow. An approved two-way cleanout fitting (Section 707.4 (5), UPC 1994) is not the same as two combination wye fittings installed with one fitting reversed to form a two-way cleanout. |
| 11/02/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/07/2005 | GERRY KOZIOL | WWM | REVIEW | Denied | needs to review location & method of connection to public sewer |
| 11/17/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approv-Cond | |
| 11/18/2005 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | Flood plain use permit required. |
| 11/25/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | Approved Development Plan and Site Plan required. |