Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM04401
Parcel: 136075680

Address:
9484 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04401
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reducing the flowrate of the supply air will not prevent recirculation of the air from the restroom if the exhaust fan is shut off with the local light switch. Reference Section 403.2.1, IMC 2000.
10/20/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. This comment was addressed but the equipment schedule still calls for a remote chiller. Clarify the position of the remote chiller for the drinking fountain; In the Janitor's room or under the sink counter? Provide an installation detail to show that the unit is being installed per the product listing. Reference Section 301.1.1, UPC 1994.
2. This comment was addressed but the two-way cleanout depicted on the waste isometric (sheet P2.0) still appears to violate Section 707.6, UPC 1994, which requires each cleanout fitting to be installed in the direction of flow. An approved two-way cleanout fitting (Section 707.4 (5), UPC 1994) is not the same as two combination wye fittings installed with one fitting reversed to form a two-way cleanout.
11/02/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Approved
11/07/2005 GERRY KOZIOL WWM REVIEW Denied needs to review location & method of connection to public sewer
11/17/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approv-Cond
11/18/2005 PAUL MACHADO ENGINEERING REVIEW Denied Flood plain use permit required.
11/25/2005 MICHAEL ST. PAUL ZONING REVIEW Denied Approved Development Plan and Site Plan required.