Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM04388
Parcel: 11205001A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04388
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Please note that the only fixtures for which lumen count does not add towards to the cap under canopies are those with full cutoff lighting distribution. Reference Tucson Lighting Code 5.1.2. Since the lighting is to be permanently installed it is not considered as temporary lighting, per the Building Official.
2. When power for exterior lighting is supplied from the energy source to the building, all exterior lighting shall have a source efficiency of 45 lumens/watt. Reference IECC 2000. Plans Examiner does not have the discretion to provide waivers on the basis of ambiance, or frequency of use.
10/21/2005 JOSE ORTIZ ENGINEERING REVIEW Denied To be approved at time of Site Plan Approval
10/25/2005 DAN CASTRO ZONING REVIEW Denied Building plans may not be approved prior to site plan approval. Assure that all structural changes have been addressed.
11/01/2005 DROBEY1 BUILDING-COMMERCIAL REVIEW Completed

Final Status

Task End Date Reviewer's Name Type of Review Description
11/01/2005 DELMA ROBEY OUT TO CUSTOMER Completed