Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM04384
Parcel: 12510004B

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T05CM04384
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Resize the drainage piping to conform to Table 7-5, UPC 1994, with no more than three 6-unit traps on a 3" horizontal waste line.
2. Coordinate the fixture-unit count, riser diagrams, and the equipment schedule shown on sheet A8.1 (e.g. dishwasher, 3 espresso machines on schedule but 2 espresso machines on the riser diagram, and the insta-hots).
3. Clarify how backflow protection is to be provided for the chemical dispensers (M075). Reference Section 603.0, UPC 1994.
4. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping and insulate the first eight feet of supply and discharge piping for the water heater. Reference Sections 804.4 and 804.5, IECC 2000.
08/24/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used by the Architect for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2000 and Section 403.3.2, IMC 2000, or an approved engineering analysis of the specific occupancy type. Reference Section 403.3, IMC 2000.
2. The minimum insulation for ducts located in unconditioned spaces within the building envelope is R-5. Reference Section 803.2.8, IECC 2000.
3. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2000.
10/12/2005 WILDAN ELECTRICAL-COMMERCIAL REVIEW Approved
10/12/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) APPROVED SITE PLAN MUST BE PROVIDED BEFORE APPROVAL OF TENANT SPACE CAN BE PROVIDED.
2) APPROVED SHELL PLANS MUST BE ISSUED BEFORE TENANT SPACE CAN BE APPROVED.
3) PROVIDE CLEAR FLOOR SPACE ENVELOPES FOR FIXTURES IN RESTROOMS.
10/21/2005 DAN CASTRO ZONING REVIEW Denied Shell building permit has not been approved as of this date 10/21/05 filed under activity number T05CM03166. The shell building plans must be approved prior to T.I. approval for Starbucks. Please attach a copy of the shell building approved plans to the T.I. plans for reference only. A copy of the stamped approved development plan/site plan must be inserted into each T.I. plan set. The copy of the stamped approved development plan submitted with the T.I. plans has not been stamped for site plan approval.

2. Dimension the exterior elevation drawings on sheet A1.0 to verify compliance with building height shown on the approved development plan/site plan.

3. This plan may be reviewed by the Zoning Review section at the counter. Please contact me at 791-5608 ext. 1180 to set an appointment.
10/31/2005 GERRY KOZIOL WWM REVIEW Denied NEEDS TO PERMIT SHELL BUILDING. WASTE WATER PERMIT #PT05SO5617

Final Status

Task End Date Reviewer's Name Type of Review Description
01/20/2006 JMORALE1 OUT TO CUSTOMER Completed
01/20/2006 SUE REEVES REJECT SHELF Completed