Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04384
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Resize the drainage piping to conform to Table 7-5, UPC 1994, with no more than three 6-unit traps on a 3" horizontal waste line. 2. Coordinate the fixture-unit count, riser diagrams, and the equipment schedule shown on sheet A8.1 (e.g. dishwasher, 3 espresso machines on schedule but 2 espresso machines on the riser diagram, and the insta-hots). 3. Clarify how backflow protection is to be provided for the chemical dispensers (M075). Reference Section 603.0, UPC 1994. 4. If the specified water heater is not supplied with integral heat traps, provide heat traps on the supply and discharge piping and insulate the first eight feet of supply and discharge piping for the water heater. Reference Sections 804.4 and 804.5, IECC 2000. |
| 08/24/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/24/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used by the Architect for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2000 and Section 403.3.2, IMC 2000, or an approved engineering analysis of the specific occupancy type. Reference Section 403.3, IMC 2000. 2. The minimum insulation for ducts located in unconditioned spaces within the building envelope is R-5. Reference Section 803.2.8, IECC 2000. 3. Provide information on the sequence of operation for the restroom exhaust to show that recirculation of the air from the restroom will not occur. Reference Section 403.2.1, IMC 2000. |
| 08/25/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/30/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 08/31/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) APPROVED SITE PLAN MUST BE PROVIDED BEFORE APPROVAL OF TENANT SPACE CAN BE PROVIDED. 2) APPROVED SHELL PLANS MUST BE ISSUED BEFORE TENANT SPACE CAN BE APPROVED. 3) PROVIDE CLEAR FLOOR SPACE ENVELOPES FOR FIXTURES IN RESTROOMS. |
| 09/28/2005 | SREEVES1 | WWM | REVIEW | Needs Review | |
| 09/28/2005 | SREEVES1 | ZONING | REVIEW | Needs Review | |
| 09/28/2005 | WILDAN | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |