Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05CM04382
Parcel: 105122910

Address:
4127 N STONE AV

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM04382
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
09/28/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM04382 .. 4127 N STONE AVENUE .. DGL .. 1ST REVIEW .. 9/29/05 ..

S1. Provide Arizona Registered Structural Engineer's analysis, sealed and signed by the Registrant addressing:
1. UNIRAC Installation Manual 214, Part II. Procedures for code-compliant installations using the Solar Mount Module Mounting System . 1. Determine the Basic Wind Speed at your installation site.
2. Determine the exposure category of your site.
3. Determine Design Wind Pressure required for your installation.
4. 4a. Determine Minimum Design Dead and Live Loads for standard rafter spacing…or 4b…Or verify Maximum Foot Spacing and Determine Minimum Design Dead Loads.
5. Verify acceptable Rail End Overhang
6. Ensure that Live Loads do not exceed Pull-Out Capacities.
2. The location drawing of the equipment on the roof showing the location dimensionally from two adjacent roof edges and showing layout orientation as well as orientation, type, size and spacing of roof framing.
3. Provide a site plan drawing locating the building and the work location on the site.
4. Show compliance with current codes, including 2003 International Building Code, see City of Tucson , DSD website : www.tucsonaz.gov/dsd, for additional information.
5. Provide completed code review checklist, downloadable from website forms section, also see attached.


Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/03/2005 GBONILL1 OUT TO CUSTOMER Completed
10/03/2005 GBONILL1 REJECT SHELF Completed