Permit Number: T05CM04357
Parcel: 11205283F

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04357
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04357 8/22/05

1. It appears that Distribution Panel DPS should be marked "Future", not "New". If it is marked new, then the design would have to be submitted for all circuits on this panel, and this does not appear to be the intent.
2. It appears that the designations for Gutter A and Gutter C are mixed up. Please correct to consistency either on the line diagram or on the load calculations.
3. The service entrance conductors entering 2000A can are labeled twice, for (5) 600 MCM and for (2) 300 MCM. It appears that the (2) 300 MCM was the error.
4. Provide fault current rating for New Panel 2C. Show fault calculations, and somehow document/demonstrate distance from service entrance.
08/22/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/22/2005 ROBERT SHERRY WATER REVIEW Approved
08/22/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/23/2005 JIM EGAN FIRE REVIEW Approved
08/23/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
08/23/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
08/23/2005 JOSE ORTIZ ENGINEERING REVIEW Approved
08/26/2005 CAGUILA1 WWM REVIEW Passed