Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04357
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/22/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM04357 8/22/05 1. It appears that Distribution Panel DPS should be marked "Future", not "New". If it is marked new, then the design would have to be submitted for all circuits on this panel, and this does not appear to be the intent. 2. It appears that the designations for Gutter A and Gutter C are mixed up. Please correct to consistency either on the line diagram or on the load calculations. 3. The service entrance conductors entering 2000A can are labeled twice, for (5) 600 MCM and for (2) 300 MCM. It appears that the (2) 300 MCM was the error. 4. Provide fault current rating for New Panel 2C. Show fault calculations, and somehow document/demonstrate distance from service entrance. |
| 08/22/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 08/22/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/22/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/23/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/23/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/23/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/23/2005 | JOSE ORTIZ | ENGINEERING | REVIEW | Approved | |
| 08/26/2005 | CAGUILA1 | WWM | REVIEW | Passed |