Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05CM04322
Parcel: Unknown

Address:
900 S PANTANO PW

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04322
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2006 VFLORES1 WATER REVIEW Needs Review
12/07/2006 WILDAN 2ND PARTY REVIEW REVIEW Denied December 6, 2006

City of Tucson Development Services
201 N. Stone Avenue
Tucson, AZ 85701

RE: PANTANO RIVER PARK – 1ST REVIEW
CITY OF TUCSON LOG NO. T06CM04322
WILLDAN PROJECT NO. 13881-6080

The initial review for the above project has been completed. This letter contains comments which need to be addressed by written responses to each which indicate any actions taken. In order to facilitate a shorter second review, all corrections and revisions must be made on the original plans and two complete new sets of prints, along with one complete redlined set, must be returned to our office. To avoid delays, ensure that all corrections have been made, are complete, and have been coordinated on all applicable detail and note sheets, and that all changes have been highlighted with appropriate revision numbers, revision dates, and “cloud bubbles.” Pen or pencil corrections on final prints are not acceptable.

This project has been reviewed for conformance with the 2003 IRC, 1997 UAC, 2003 IMC, 2003 IECC, 2002 NEC codes with local modifications, and the 2003 UPC with State of Arizona Amendments. Any revisions to this plan will require an additional review and approval by Willdan.

Should you have questions regarding the comments herein, please contact your plans examiner Jim Singleton.

Occupancy Occup. Load Construction Area S.F. Sprinklered Alarms
U N/A V-B N/A No No

Special Inspection is required for the following items:
N/A

The following items are acceptable for deferred submittals:
N/A

GENERAL COMMENTS:
See additional comments by City Zoning, Engineering, Landscaping, and Accessibility review staff and resolve their comments. IBC Sec. 106.1.1.

ARCHITECTURAL COMMENTS:
Sheet A1
The drinking fountains at the comfort stations shall be of the type that provides access for the physically disabled, usually a dual level type. Reference IBC Section 1109.5, 2003 ICC/ANSI 117.1, Section 602 and ADDAG Section 4.15.

All protruding objects and freestanding objects shall provide “cane” detectable warning as required by ADDAG Section 4.4.

On the interior wall section/elevations of the toilet rooms, provide the dimensions for mounting the 18” vertical grab bars. The centerline shall be at a minimum of 39” to a maximum of 41” from the rear wall and the bottom edge shall be a minimum of 39” to a maximum of 41” above the floor. Reference 2003 ICC/ANSI 117.1, Section 604.5.1.

STRUCTURAL COMMENTS:
The structural calculations and plans for the comfort stations buildings have been reviewed and accepted.

PLUMBING COMMENTS:
Sheet AP1
The Under Floor Plumbing Plan does not show the 2 lavatories or the 2 drinking fountains. Please revise to correct this discrepancy. Reference 2003 UPC Section 103.2.3.

Please correct the Sewer and Vent Riser diagram to agree with the plan and fixture layout. Reference UPC Section 103.2.3.

Clarify that the water heaters shall be equipped with heat traps on both the hot and cold water pipes. Reference IECC Section 804.4.

Show how the hot water outlet temperature at the lavatories shall be limited to 110 degrees. Reference IECC Section 804.3.

Provide insulated drainpipe and hot water pipe at the lavatories or other means to prevent accidental contact by the handicapped. Reference ICC/ANSI 117.1 Section 606.6.

MECHANICAL COMMENTS:
Not part of this review.

ELECTRICAL COMMENTS:
The electrical plans have been reviewed and accepted, subject to showing the circuit breaker size for the lights on Panel A, Circuits 2, 4 & 6. Reference IBC Section 106.1.1.

ENERGY CODE COMMENTS:
The plans have been reviewed for compliance with the 2003 IECC and accepted, subject to correcting the architectural and plumbing comments above.

ACCESSIBILITY COMMENTS:
See the accessibility comments by the City Accessibility plan reviewer and correct each item as required. Reference IBC Section 106.1.1.

Sincerely,

WILLDAN




Martin Haeberle, C.B.O.
Building Official

MAH/tb
12/07/2006 VFLORES1 ENGINEERING REVIEW Needs Review
12/07/2006 WILLDAN ADA REVIEW Denied These plans have been reveiwed by the City of Tucson Office of Equal Opportunity Programs for compliance with Department of Justice 28 CFR Part 36 ADA Standards for Accessible Design revised July 1, 1994. These guidelines are available for download at ada.gov

1. Identify the accessible route on the plans. §4.3
2. All walks identified as part of the accessible route shall not have a running slope greater than 5% or it will be considered a ramp. Provide a passing space at intervals not to exceed 200' and free of protruding objects. §§§4.3.4, 4.3.7, 4.4
3. Walking surfaces to comply with section §4.5
4. Insure that tree limbs located in the accessible path allow 80" minimum headroom. §4.6.4
5. Demonstrate on the plans at the HC parking spaces and access aisles that the slope does not exceed 2% in any direction. §4.6.3
6. Specify accessible picnic tables. §§4.1.3(18), 4.32 & Fig. 45
7. Detail #1 on sheet SP-15. The change in ground surfaces shall comply with §4.5 for elevation.
8. Plan #1 on sheet SD-1. Provide access aisle at the parallel HC parking space. §4.6.3
9.Detail #2 on sheet D-3. Handrail diameter is called out as 1 5/8". Diameter shall be 1 1/4" to 1 1/2" and required on both sides of the steps. The maximum raius on the nosing is 1/2". Handrail to extend 12" minimum beyond the top riser and at least 12" plus the width of of one tread beyond the bottom riser. At the top the extension shall be parrallel with the floor or ground surface. At the bottom the handrail shall continue to slope for a distance of the width of one tread from the bottom riser; the remainder of the extension shall be horizontal. The extension shall not create a protruding object.
10. Detail #8 &#9 on sheet D-5. Change 4'-0' bottom of sign dimension to 7'-0". §4.6.4
11. Detail #13 on sheet D-5. The cable strung between the bollards is not cane detectable. §4.4, Fig. 8(c)
12. Detail #1 on sheet D-6. Truncated domes to be located in the depressed section of the sidewalk. Pedestrian area to vehicular area. §4.7..7
13. Detail #5 on sheet D-6. Change note #11 to read truncated domes. §4.7.7
14. Detail #3 on sheet D-7. Change tactile warning to truncated domes. §4.7.7
15. Drinking fountains and lavatory's are located in the accessible path of travel and are protruding objects, provide cane detectability. §4.4
16. Show mounting height of lavatory's. §4.19
17. Provide hi/lo drinking fountains and dimension mounting heights. §4.15
18. Dimension location of side & rear grab bars from side & rear walls. §4.17, Fig. 30
19. Toilet height is measured to the top of seat 17" to 19". §4.16.3
20. Show location and height of flush control. §4.16.5
21. Show location, type and mounting height of required accessible signage. §4.30
22. The 1'-6" dimension is absolute from finish of side wall to center of toilet. Delete the "MIN." §4.17, Fig. 30
12/08/2006 SREEVES1 ZONING REVIEW Needs Review
12/08/2006 SREEVES1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
12/11/2006 CINDY AGUILAR OUT TO CUSTOMER Completed
12/11/2006 SUE REEVES REJECT SHELF Completed