Permit Number: T05CM04309
Parcel: 14113017A

Address:
9314 E RITA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04309
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
02/06/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.
INCLUDE EMAIL ADDRESS OF ENGINEER/ARCHITECT/DESIGNER WITH NEXT SUBMITTAL
PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Charge controller shall be listed equipment. UNRESPONSIVE TO COMMENT MADE 9/19/05, 11/10/05, AND 12/22/05. Provide a hard copy from the Independent Testing Laboratory proving that this item is listed. Did not find such documentation in the present submittal.
2. Provide listing information on the lighting fixture. UNRESPONSIVE TO COMMENT MADE 9/19/05, 11/10/05, AND 12/22/05. Provide hard copy of such certification as a device which consumes DC power, from the Independent Testing Laboratory. Did not find such documentation in the present submittal. Present submittal contains a cht sheet for a luminaire that is AC powered.
3. Photovoltaic submittal shall include complete design for a Code-compliant installation, on details/line diagrams. Comments below are representative.
4. Show the sizing and location of all overcurrent devices per NEC 690.8 and 690.9.
5. Specify on installation detail/line diagram all conduit and conductor sizes and types.
6. Specify all required grounding on installation detail/line diagram. Reference NEC 690 Part VI, 250.169.
7. Specify the marking per NEC 690.53, on installation detail/line diagram.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/07/2006 GBONILL1 OUT TO CUSTOMER Completed
02/07/2006 SUE REEVES REJECT SHELF Completed