Permit Number: T05CM04309
Parcel: 14113017A

Address:
9314 E RITA RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04309
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.
INCLUDE EMAIL ADDRESS OF ENGINEER/ARCHITECT/DESIGNER WITH NEXT SUBMITTAL
PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Provide listing information for the X-35 as a system, or the Plans Examiner will have to continue this review by considering each item separately, and then the system as a whole.
2. Specify exactly which lamp is to be used, on the plans. The cut sheet has both HPS and Merc fixtures. Mercury Vapor is prohibited per the Tucson Lighting Code, Section 10.1.
3. It is not clear which solar panel is to be used, the GEPV-050 or the GEPV-030.
4. Panel specifications indicate that these are GE panels. Battery enclosure specifications reference Seimens Solar modules. Please clarify.
5. Regarding Keynotes 34, 38, 39 and all others which may apply, provide a panel and circuit, and accounting in load calculations for the new signing if part of this project. If the intent is to have the signing be done by others, or to be done under a separate permit, or to be future, indicate such on the plans.
11/18/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 11/18/05
ACTIVITY NUMBER: T05CM04309
PROJECT NAME: LIGHTING
PROJECT ADDRESS: 9314 E. RITA RD.
ARCHITECT / ENGINEER: RS ENGINEERING

1) Specify E1.1 - detail 2 and E2.1- detail 3 reinforcing per structural calcs. sht.4 .
2) Structural Engineer needs to stamp and sign details provided on drawings.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/28/2005 CINDY AGUILAR OUT TO CUSTOMER Completed
11/28/2005 SUE REEVES REJECT SHELF Completed