Permit Number: T05CM04291
Parcel: 11005528A

Review Status: Stopped

Review Details: COMMERCIAL TI

Permit Number - T05CM04291
Review Name: COMMERCIAL TI
Review Status: Stopped
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2006 EROSE1 BUILDING-COMMERCIAL REVIEW Stop
08/17/2005 ANY WWM REVIEW Stopped
08/18/2005 JIM EGAN FIRE REVIEW Approved
08/18/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a cut sheet for the proposed water heater. Reference Section 501.0, UPC 1994.
2. Limit the connected waste fixture units connected to a 2" waste pipe to 8 fixture units. Reference Table 7-5, UPC 1994.
3. Provide a riser diagram for the water piping.
4. Provide insulation for the first 8 feet of piping from the water heater. Reference Section 803, IECC 2000.
08/18/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied t05cm04291
8/18/05

1. Mechanical calls for single phase AC. Electrical provides 3-phase power. Coordinate with Mechanical and clarify.
2. MCA is 46.3A per Mechanical. The 40A Ckt is not adequate.
3. Service is 120/208V. Panel is set up as if for 120/208, but is noted as a 240/120. Please clarify.
4. Put Panel D on line diagram. Note that Keynote 8, for Panel ES, was used in 2 places.
5. Add the following note in a prominent place on the plans: "All work in patient care areas shall be installed in accordance with the reQuirements of NEC 517.13."
08/18/2005 ROBERT SHERRY WATER REVIEW Approved
08/18/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
08/18/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Show how the exhaust fan in the restroom will be controlled to prevent recirculation of air from the restroom.
08/18/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2005 ANY APPROVAL SHELF Stopped
08/17/2005 ANY OUT TO CUSTOMER Stopped
08/17/2005 ANY REJECT SHELF Stopped