Permit Number: T05CM04285
Parcel: 12412293A

Address:
301 S PARK AV

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04285
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/06/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM04285.. 301 SOUTH PARK AVENUE .. MULI-PHASE EXTRACTION REMEDIATION SYSTEM MISSION LINEN SUPPLY .. DGL .. 1ST REVIEW .. 10/07/05 ..


S1. Show and annotate property lines on site plan C-1.
S2. Dimensionally locate items requiring permitting on drawing C-1 from two adjacent property lines and within the building.
S3. Provide completed Code Review Checklist for building.
S4. Provide drawings, structural calculations and specifications necessary to issue a building permit for:
1. 6500 gallon water tank (Treated Water Storage Tank)
2. 8' High Framed Partition Wall
3. 4 - Interior Well Head Vaults, including Vault Cover
4. 2 - Exterior Well Head Vaults, including Vault Cover.
5. Roof Vent.
S5. Convault Product Tank by separate permit from TFD.
S6. Address accessibility per IBC Section 34, 11 and ANSI A117.1-2003ed.
S7. Show building Occupancy on drawings and Code Review Checklist per IBC Section 3.
S8. Show building Type of Construction on drawings and Code Review Checklist per IBC Section 6.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
10/11/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Electrical Engineer shall identify the extent of the Classification recommended in the letter from Janet M. Workman, dated August 9, 2005. Provide detailed specifications for any electrical equipment installed in and above this area, and cut sheets of acceptable products.
2. Provide specifications for the Packaged Multiphase Extraction System Control Panel, and cut sheets of acceptable products if available. Include listing information.
3. Specify rating and type of all Overcurrent Protective Devices for new equipment.
4. NEC 230.2 limits each building to one electrical service. If a second service is justified under the provisions of this Section, please clarify such on the plans, and provide specific wording for the placards required by 230.2 (E).
5. Any new electrical service shall be underground, not overhead, in the City of Tucson.
6. Keynote 11 Sheet E-2 specifies an exhaust fan to be powered by the Owner. Provide panel and circuit number, conduit and conductor size and type, feeder overcurrent protection, and load calculations.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/18/2005 DELMA ROBEY OUT TO CUSTOMER Completed
10/18/2005 SUE REEVES REJECT SHELF Completed