Permit Number: T05CM04276
Parcel: 107060560

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04276
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2005 JIM EGAN FIRE REVIEW Approved
09/12/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. City of Tucson Ordinance 1802 requires a reduced pressure backflow preventer to be located immediately after the water meter. Please show the RPBP on the drawings and include the pressure drop on the water calculations. Reference Section 103.2.3, UPC 1994.
2. Potable water outlets with hose connections are required to comply with Section 603.3.6, UPC 1994 with AZ State amendments.
3. Specify the materials to be used for the water piping and fittings. Reference Section 604.1, UPC 1994.
4. Provide water pressure and water pipe sizing calculations. Include all fixtures planned for the security office when calculating the total demand and determining pipe sizes. Reference Section 610.1 and Appendix A, UPC 1994.
5. Specify the materials to be used for the drainage piping and fittings. Reference Section 701.0, UPC 1994.
6. The indicated invert of the HCS (2345.2) is higher than the invert of the initial cleanout for the building sewer (2310.5). If this is correct, provide a lift station, approved by Pima County Wastewater Engineering per Section 710.2, UPC 1994.
09/12/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/12/2005 ROBERT SHERRY WATER REVIEW Denied Provide a reduced pressure backflow preventer, located immediately after the water meter, per City of Tucson Ordinance 1802.
09/20/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied Approved Site plan is required prior to building plan approval.
09/26/2005 GERRY KOZIOL WWM REVIEW Passed
09/30/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Demonstrate compliance with the Tucson Lighting Code.
10/14/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM04276 .. 1315 WEST MIRACLE MILE ROAD .. CONSTRUCTION MATERIAL STORAGE YARDS .. DGL .. 1ST REVIEW .. 10/14/05 ..


S1. Clarify accessible route through the site including sidewalks, accessible parking, provide adequate finish grade elevations to show conformance with IBC Section 11 and ANSI A117.1 - 2003ed.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
10/18/2005 DAN CASTRO ZONING REVIEW Denied Building plans may not be approved prior to site plan approval. Please assure that the building size, height, and location shown on the building plans match what is shown on the approved site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/31/2005 SPOWELL1 OUT TO CUSTOMER Completed
10/31/2005 SUE REEVES REJECT SHELF Completed