Permit Number: T05CM04276
Parcel: 107060560

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04276
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2006 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Approved
03/01/2006 MARTIN BROWN FIRE REVIEW Approved
03/02/2006 PATRICIA GILBERT ENGINEERING REVIEW Denied Approved site plan is required prior to building plan approval.
03/20/2006 ROBERT SHERRY WATER REVIEW Approved
03/21/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The water pressure and water pipe sizing calculations incorrectly use a developed pipe length of 45 feet. The developed length from the water meter to the furthest outlet appears to be approximately 295 feet. The pipe sizes, however, appear to be adequate. Reference Appendix A, UPC 1994.
2. A 3" building sewer may not be installed with a slope less than ¼" per foot. (A 4" building sewer is allowed to have a slope as low as 1/8" per foot if a slope of ¼" per foot is impractical due to the depth of the public sewer or structural conditions.) Reference Section 718.1, UPC 1994.
04/21/2006 TERRY STEVENS ZONING REVIEW Denied 04/22/06

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

Two copies of the approved and stamped site plan required prior to approval of the building plan.

Zoning will re-review the building plans on the next submittal to ensure compliance with the approved site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/26/2006 GBONILL1 OUT TO CUSTOMER Completed