Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM04242
Parcel: 12619188P

Address:
4343 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04242
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Second request. The "2-way cleanout" shown in detail 3/03 is in violation of Section 707.6, UPC 2003. Exception 4, Section 707.4, UPC 2003 allows for the substitution of "an approved two-way cleanout fitting" if an upper terminal cleanout cannot be installed. An approved two-way cleanout fitting is a singular fitting and not an assemblage of fittings.
03/15/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied An approved site plan is required prior to building plan approval.
03/20/2007 TERRY STEVENS ZONING REVIEW Denied building plans cannot be approved until the site plan has been stamped and approved by all sections of DSD.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/10/2007 GERARDO BONILLA OUT TO CUSTOMER Completed
04/10/2007 SUE REEVES REJECT SHELF Completed