Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/13/2007 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Second request. The "2-way cleanout" shown in detail 3/03 is in violation of Section 707.6, UPC 2003. Exception 4, Section 707.4, UPC 2003 allows for the substitution of "an approved two-way cleanout fitting" if an upper terminal cleanout cannot be installed. An approved two-way cleanout fitting is a singular fitting and not an assemblage of fittings. |
03/15/2007 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | An approved site plan is required prior to building plan approval. |
03/20/2007 | TERRY STEVENS | ZONING | REVIEW | Denied | building plans cannot be approved until the site plan has been stamped and approved by all sections of DSD. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/10/2007 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |
04/10/2007 | SUE REEVES | REJECT SHELF | Completed |