Permit Number: T05CM04242
Parcel: 12619188P

Address:
4343 E 22ND ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04242
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/06/2007 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The "2-way cleanout" shown in detail 3/03 is in violation of Section 707.6, UPC 2003. Exception 4, Section 707.4, UPC 2003 allows for the substitution of "an approved two-way cleanout fitting" if an upper terminal cleanout cannot be installed. An approved two-way cleanout fitting is a singular fitting and not an assemblage of fittings.
02/07/2007 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
02/20/2007 PATRICIA GILBERT ENGINEERING REVIEW Denied Teh site plan must be approved prior to building plan approval. Once the site plan is approved by all reviewing sections, submit the site plan with the building plan.
03/02/2007 TERRY STEVENS ZONING REVIEW Denied building plans cannot be approved until the site plan has been stamped and approved by all sections of DSD.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/08/2007 FSANCHE1 OUT TO CUSTOMER Completed
03/08/2007 SUE REEVES REJECT SHELF Completed