| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/01/2006 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 03/13/2006 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | It appears that the 2 feeders to the modular panels violate the requirements of 225.30 . |
| 03/16/2006 | PATRICIA GILBERT | ENGINEERING | REVIEW | Denied | An approved site plan is required prior to building plan approval. |
| 03/20/2006 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide the listing for the two-way cleanout fitting called out on the Utility Site Plan. Reference Sections 103.2.3 and 707.6, UPC 2003. |
| 04/20/2006 | TERRY STEVENS | ZONING | REVIEW | Denied | building plans cannot be approved until the site plan has been stamped and approved by all sections of DSD. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/25/2006 | DELMA ROBEY | OUT TO CUSTOMER | Completed |