Permit Number: T05CM04242
Parcel: 12619188P

Address:
4343 E 22ND ST

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04242
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Passed
01/17/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied Note on Sheet A 01 refers to electrical plans. Provide such electrical plans with next submittal.
01/18/2006 GERRY KOZIOL WWM REVIEW Approved
12/20/2005 TERRY STEVENS ZONING REVIEW Denied 12/20/05

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner


Building Plans: T05CM04242

Comments:

1. Building elevations and a floor plan must be provided in order to complete the zoning portion of the building review.

2. Zoning will review and approve the building plans once the structural and commercial reviewers have approved the building plans.

3. This review can be done over the counter. Please contact me to set an appointment.

If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.
12/21/2005 JIM EGAN FIRE REVIEW Denied A minimum 20 feet wide, paved, fire access roadway must be provided and extended to within 150 feet of all portions of the exterior walls of all structures. An approved turnaround is required for dead-end access roadways.
12/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide justification for connecting the drainage system of the new modular building to the building drain of the existing building. Reference Section 312.0, UPC 1994.
2. Show the size, inverts and slope of the both the proposed building sewer (from the modular building) and the existing building drain on the drawing. The slope of the building sewer shall be at least ΒΌ" per foot unless it is shown to be impractical due to the depth of the public sewer or structural conditions. Reference Sections 103.2.3 and 718.1, UPC 1994.
3. Show the location of the cleanouts in the building sewer. Reference Section 719.1, UPC 1994.
4. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 1994.
5. Provide CW shut off valves for each building entrance. The valves shall be accessible at all times and arranged so that the water service to the individual buildings can be controlled. Reference Section 605.3, UPC 1994.
12/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
12/28/2005 ROBERT SHERRY WATER REVIEW Approved
12/30/2005 LOREN MAKUS ENGINEERING REVIEW Denied The building plan cannot be approved until the site plan has been approved.