Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM04242
Parcel: 12619188P

Address:
4343 E 22ND ST

Review Status: Completed

Review Details: SITE

Permit Number - T05CM04242
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/06/2005 JIM EGAN FIRE REVIEW Denied A minimum 20 feet wide, paved, fire access roadway must be provided and extended to within 150 feet of all portions of the exterior walls of all structures. An approved turnaround is required for dead-end access roadways.
12/13/2005 TERRY STEVENS ZONING REVIEW Denied DSD TRANSMITTAL

FROM: Terry Stevens FOR: David Rivera
Senior Planner Principal Planner

PROJECT:T05CM04242
4343 E. 22nd St.
Modular Building
Site Plan

Transmittal date:1st Review 12-16-05

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Provide the last stamped and approved site plan as well as a dimensioned floor plan of the existing structure. These documents are required in order to complete the review.

2. As per Pima County Assessors records the site plan of the lot provided and the lot to the north of this property appears to have been reconfigured along the west side of the properties and the lot line between the two lots. One of the questions is where did the additional 15' come from indicated at the west property line. Provide documentation and stamped and approved plans indicating that the City of Tucson has approved the reconfigurations.
Per the data project information provided it is unclear if portions of the vacant properties are being added to the site. If this is correct the addition of property or parking spaces (paving) may cause the expansion to be greater than 25%, thus requiring full code compliance for the entire site.

If you feel it would be necessary for clarification concerning these comments please feel free to call me for an appointment to discuss these issues.

3. DS 2-02.2.1.2 Provide the legal description of the property.

4. DS 2-02.2.1.5 Provide dimensions and bearings for all lot lines.

5. DS 2-02.2.1.8 The backup spur located near parking space #29 does not meet the requirements of DS 3-05 Figure 2. Required 3' radius, 3' depth, and 3' space behind the curb.

6. DS 2-02.2.1.9 Please clarify the required and existing bicycle parking spaces. The project data information is indicating there are no bicycle parking spaces required which is incorrect. See LUC Sec. 3.3.4 for required number of spaces for Religious Use and Educational Use. For off street bicycle parking provide the full dimensioned layout, paving, detail of specific type of rack and number of bicycles it supports, and as it appears the bicycle parking spaces are not visible from the adjacent street provide directional signage.

7. DS 2-02.2.1.11 The new paving along the north side of the lot will require curb or barricades to prevent vehicles from driving on to the vacant lot to the north. See DS 3-05.2.3.C.1.

8. DS 2-02.2.1.12 A sidewalk will be required along the north and west side of the modular building. Sidewalks are required between a PAAL and a building. See DS 2-08.4.1.B.

A handicap ramp is required at the sidewalk adjacent to the new crosswalk for the handicap parking spaces.

Access ramps at crosswalks connecting to sidewalks must be provided. In addition Truncated Dome (early warning systems) must be added to all access ramps where transitioning from the pedestrian area to the vehicular use area or at HC access aisles transitioning to the sidewalk area.

9. DS 2-02.2.1.20 If applicable, all easements of record must be graphically shown on the plan together with recording docket and page.

10. DS 2-02.2.1.25 If applicable, provide existing or proposed lighting layout.

11. DS 2-02.2.1.28 Provide the existing zoning of adjacent properties. The vacant lots to the north and east of the proposed site have split zoning R1 and C2. Clearly indicate the correct adjacent zoning. For exact location of the zoning boundaries contact Harold Schwartz @ 791-5550 ext. 1162.

12. DS 2-02.2.1.31 Provide the existing and proposed use. It appears the property will have both Religious and Educational Uses. Provide a project data matrix for the Educational use including the subject to sections of the LUC.

LUC Sec. 2.5.4.2.C.4 Educational use: Elementary and Secondary Schools "31", subject to: 3.5.3.7

The above subject to section requires:
A. Licensing. If licensing, certification, or similar type of approval is required by the State of Arizona for the use, proof of such licensure, certification, or approval shall be provided. Such information shall include the number of students for which the school is approved. (Ord. No. 9392, ยง1, 5/22/00)
Zoning compliance shall not be granted for an Educational Use which has approval from the authorizing agency for more students than can be accommodated on the site in accordance with zoning requirements.

13. DS 2-02.2.2 Calculations:

The calculation for lot area may change based on response to comment #2.

Provide the FAR (Floor Area Ratio) for the project. Max. FAR has been provided but not the proposed.

Bicycle parking calcs. are not correct. See comment #6.

The percentage of lot expansion may change based on response to comment #2.

14. See redlined plan for clarification.

15. If it is determined that full code compliance is required a site plan drawn to all the specifications of DS 2-02 will be required.

16. Based on responses to comments and changes to the plans further comments may be forth coming.


If you have any questions about this transmittal, please call Terry Stevens, (520) 791-5550 ext. 2000.
12/20/2005 ANDREW CONNOR NPPO REVIEW Denied Submit NPPO plan or application for exception
12/20/2005 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. Submit last stamped approved site plan including landscape plan to continue review.

2. Provide legal description of property on site plan per DS 2-02.2.1.2

3. A 5' wall is required to screen vehicle use area from residential zones within 100-ft per LUC3.7.2-I. Portion of the property to the north is residentially zoned.

4. Submit NPPO plan or application for exception per DS2-15.0

5. Additional comments may apply per zoning division comments regarding expansion calculations.
12/20/2005 TERRY STEVENS ZONING HC SITE REVIEW Denied see zoning comments
12/30/2005 LOREN MAKUS ENGINEERING REVIEW Denied January 3, 2006
TO: Rick Stevenson, Living Waters Ministry
SUBJECT: Site Plan
REVIEWER: Loren Makus
ACTIVITY NUMBER: T05CM04242

SUMMARY: The Site Plan was reviewed by Development Services Department, Engineering Division on January 3, 2006. The Site Plan was not approved at this time. Please address the following comments.

Site Plan Comments:
1. Provide bearings for each property boundary. (DS 2-02.2.1.A.5)
2. Provide existing and future sight visibility triangles for the driveway. Since Columbus is an MS&R collector, take into account the potential future widening of 22nd Street. (DS 2-02.2.1.A.10)
3. Provide estimated cut and fill quantities. (DS 2-02.2.1.A.17)
4. Dimension the adjacent right-of-way. Include the locations of existing and proposed curbs, sidewalks, and utility lines. Indicate that 22nd Street is an MS&R route. (DS 2-02.2.1.A.19 and 21)
5. Show the solid waste container location and show how solid waste vehicle will access the container. (DS 2-02.2.1.A.32)
6. Show Drainage patterns, proposed finish floor elevation(s), and finish grades. (DS 2-02.2.1.A.16)
7. Show that the sidewalk areas adjacent to the modular will be kept flood free for up to a 10-year event.

Revise the Site Plan to address all of these comments and resubmit two copies for review. Include a letter explaining how each comment has been addressed. If you have any questions or if you wish to discuss any of these comments, I can be reached at 520.791-5550 ext 1161 or by email at loren.makus@tucsonaz.gov.
Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2006 JMORALE1 OUT TO CUSTOMER Completed
01/26/2006 SUE REEVES REJECT SHELF Completed