Permit Number: T05CM04228
Parcel: 10609062C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04228
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05CM04228 .. 3923 N FLOWING WELLS ROAD .. REMODEL GROCERY STORE .. DGL .. 2nd REVIEW .. 10/05/05 ..


Comply with prior comments S1 through S8, listed below.
S1. Coordinate Architectural and Structural Drawings roof is made of wood trusses and plywood decking revise details to conform to existing construction.
S2. Details 1/A2 and 6/A2: show corrected materials and connections to structure above with fastener type, size, spacing/number indicated on detail.
S3. Pima County Health Department review and approval required prior to issuance of Building Permit.
S4. Provide Architectural Details for: roof drainage, flashing and weather protection at roof mounted equipment, IBC Chapter 15.
S5. Coordinate Architectural, Structural and Mechanical Drawings for roof penetrations, where are they and what is the size and shape.
S6. Show drawings are per 2003 International Building Code, ref T-1.
S7. Detail structural connections of equipment to roof, including TS to roof trusses, hangers to roof trusses, equipment curb to TS and plywood to new roof framing, etc.
S8. Show in structural calculations that the equipment weight includes: 1. Equipment operating weight, plus 2.The weight of the curb, plus 3. The weight of all ducts supported by the equipment, plus 4. The weight of the added support structure.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111
10/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The ice machine, D11b, and the 6-well hot food table, D2, are to be directly connected to the water supply system. If they do not have listed, integral backflow preventers or integral air gaps, show how possible backflow is being addressed. Reference Section 603.0, UPC 1994.
10/20/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/02/2005 DELMA ROBEY OUT TO CUSTOMER Completed
11/02/2005 DELMA ROBEY REJECT SHELF Completed