Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM04228
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/05/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T05CM04228 .. 3923 N FLOWING WELLS ROAD .. REMODEL GROCERY STORE .. DGL .. 2nd REVIEW .. 10/05/05 .. Comply with prior comments S1 through S8, listed below. S1. Coordinate Architectural and Structural Drawings roof is made of wood trusses and plywood decking revise details to conform to existing construction. S2. Details 1/A2 and 6/A2: show corrected materials and connections to structure above with fastener type, size, spacing/number indicated on detail. S3. Pima County Health Department review and approval required prior to issuance of Building Permit. S4. Provide Architectural Details for: roof drainage, flashing and weather protection at roof mounted equipment, IBC Chapter 15. S5. Coordinate Architectural, Structural and Mechanical Drawings for roof penetrations, where are they and what is the size and shape. S6. Show drawings are per 2003 International Building Code, ref T-1. S7. Detail structural connections of equipment to roof, including TS to roof trusses, hangers to roof trusses, equipment curb to TS and plywood to new roof framing, etc. S8. Show in structural calculations that the equipment weight includes: 1. Equipment operating weight, plus 2.The weight of the curb, plus 3. The weight of all ducts supported by the equipment, plus 4. The weight of the added support structure. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111 |
| 10/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The ice machine, D11b, and the 6-well hot food table, D2, are to be directly connected to the water supply system. If they do not have listed, integral backflow preventers or integral air gaps, show how possible backflow is being addressed. Reference Section 603.0, UPC 1994. |
| 10/20/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/02/2005 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 11/02/2005 | DELMA ROBEY | REJECT SHELF | Completed |