Permit Review Detail
Review Status: Completed
Review Details: POST 3RD PARTY REVIEW
Permit Number - T05CM04213
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/14/2005 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 09/14/2005 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 09/14/2005 | JIM EGAN | FIRE | REVIEW | Denied | 1. Minimum one-hour fire barrier required between warehouse and offices per 2003 IBC Section 302.2 and Table 302.1.1. |
| 09/14/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 09/14/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/16/2005 | CINDY AGUILAR | APPROVAL SHELF | Completed |
| 09/16/2005 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |