Permit Number: T05CM04199
Parcel: 14027044B

Address:
6251 S TUCSON BL

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04199
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/02/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
09/02/2005 ROBERT SHERRY WATER REVIEW Approved
09/07/2005 TERRY STEVENS ZONING REVIEW Denied 1. Zoning has reviewed the building plans but cannot approve them at this time. Zoning will re-review and approve the building plans on the next submittal providing the stamped and approved site plans are included with the building plan package.
09/08/2005 JIM EGAN FIRE REVIEW Denied 1. Minimum 2-hour fire rated exterior wall required for South Wall located less than 5'-0" from property line. Minimum 30-inch parapet required.
09/15/2005 LOREN MAKUS ENGINEERING REVIEW Denied Site plan must be approved before the building plan can be approved.
09/20/2005 SEPTIC APPROVAL WWM REVIEW Approved
09/23/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Denied City of Tucson, Development Services
BUILDING AND STRUCTURAL COMMENTS
9/26/05

1) Provide a 2 hour rated wall at south side of building with a 30" parapet. Show
detail of rated wall.
2) Show location of existing bathrooms, including physically handicpped unit.
3) Specify the wind force that the structure is designed for.
4) How is the wind force resisted by the structure in the longitudinal direction?
09/29/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Air Compressor listed as 230V on Electrical, but is powered at 208V according to the panel schedule. Please clarify.
2. Air compressor (2400) (2) / 208 = 23.1 A. This does not correspond to a 5 HP motor in either the 208V or 230V class, according to NEC Table 430.148.
3. Demonstrate compliance with 2000 IECC.
4. Address the grounding requirements of NEC 250.32 for Two or More Buildings Supplied From a Common Service.
5. Provide fault current at electrical service.
6. Provide fault calculations for AFC at New Panel S.
7. Provide fault current rating of New Panel S.

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2005 JMORALE1 OUT TO CUSTOMER Completed
11/08/2005 SUE REEVES REJECT SHELF Completed