Permit Number: T05CM04199
Parcel: 14027044B

Address:
6251 S TUCSON BL

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04199
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/15/2005 JIM EGAN FIRE REVIEW Approved
11/18/2005 LOREN MAKUS ENGINEERING REVIEW Approved
11/29/2005 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
12/05/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Air compressor has correct load information, but this is for a 30.8A piece of equipment. A 30A Circuit Breaker would trip with normal loading, and may not even allow the equipment to start.
2. Please change "MLO" on New Panel S Schedule to read "MCB". In this way, we provide for the disconnect per NEC 225.31.
3. Note that the City of Tucson does not allow the "Up-Over-Down" method for determining fault calculations. Rework fault calculations without the use of the Let-Through current.
12/07/2005 TERRY STEVENS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/12/2005 GBONILL1 OUT TO CUSTOMER Completed
12/12/2005 SUE REEVES REJECT SHELF Completed