Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM04199
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/15/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 11/18/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 11/29/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/05/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL. PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov IF YOU CARE TO DISCUSS. 1. Air compressor has correct load information, but this is for a 30.8A piece of equipment. A 30A Circuit Breaker would trip with normal loading, and may not even allow the equipment to start. 2. Please change "MLO" on New Panel S Schedule to read "MCB". In this way, we provide for the disconnect per NEC 225.31. 3. Note that the City of Tucson does not allow the "Up-Over-Down" method for determining fault calculations. Rework fault calculations without the use of the Let-Through current. |
| 12/07/2005 | TERRY STEVENS | ZONING | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/12/2005 | GBONILL1 | OUT TO CUSTOMER | Completed |
| 12/12/2005 | SUE REEVES | REJECT SHELF | Completed |