Review Date Reviewer's Name Type of Review Description Status Comments
08/18/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM04189
8/17/05

1. See Comment #2 on the previous review. It appears that the lighting was calculated on the basis of 100VA per fixture. According to the New Lighting Fixture Schedule, the correct multiplier is 128, for the 4 32W fixtures.
2. Same as comment #1 above for Ckts 7 and 9.
3. Same as above for Ckts, 1, 3, and 5.
4. Heat pumps are in revision cloud without revision triangle, so it is unclear when this change has been made. Mechanical calls for single phase power. Electrical provides 3-phase power. Coordinate with Mechanical and clarify.