Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM04189
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/18/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM04189 8/17/05 1. See Comment #2 on the previous review. It appears that the lighting was calculated on the basis of 100VA per fixture. According to the New Lighting Fixture Schedule, the correct multiplier is 128, for the 4 32W fixtures. 2. Same as comment #1 above for Ckts 7 and 9. 3. Same as above for Ckts, 1, 3, and 5. 4. Heat pumps are in revision cloud without revision triangle, so it is unclear when this change has been made. Mechanical calls for single phase power. Electrical provides 3-phase power. Coordinate with Mechanical and clarify. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/18/2005 | KMEDINA1 | OUT TO CUSTOMER | Completed |