Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM04189
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/12/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 08/12/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM04189 1. Identify panel and circuits for new bathroom receptacles. Add to panel schedule. 2. Circuit 2 appears to be undercounted on panel schedule. 12 Fixture E and 3 Fixture B yields 2400VA at continuous load. 3. Circuit 7 appears to be overloaded as well. 4. Second grouping from the right of luminaires is on Ckts 7 and 9, but it is unclear which luminaires are on which circuits. 5. Please re-evaluate all lighting branch circuits per the above comments, and correct panel schedule as necessary. |
| 08/15/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved |