Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/12/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/12/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04189

1. Identify panel and circuits for new bathroom receptacles. Add to panel schedule.
2. Circuit 2 appears to be undercounted on panel schedule. 12 Fixture E and 3 Fixture B yields 2400VA at continuous load.
3. Circuit 7 appears to be overloaded as well.
4. Second grouping from the right of luminaires is on Ckts 7 and 9, but it is unclear which luminaires are on which circuits.
5. Please re-evaluate all lighting branch circuits per the above comments, and correct panel schedule as necessary.