Permit Number: T05CM04185
Parcel: 13613016C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04185
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2006 JIM EGAN FIRE REVIEW Approved
01/13/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
01/17/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The water calculation note on sheet M4 addresses pipe locations but does not consider either pipe sizes or the water pressure available for friction in the existing water system. Show how the new water piping relates to the existing water supply system and show that the additional connections do not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 1994.
2. The water calculation note on sheet M4 addresses pipe location but does not provide any information regarding the water pressure available for friction in the existing water system. Show how the new water piping was sized.
3. The existing cleanout is still shown opening opposite the direction of flow. Clarify the direction of flow of the building drain as shown in detail 1/M2. Reference Section 707.6, UPC 1994.
01/17/2006 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the balancing information per Section 403.3.2, IMC 2000.
2. The basis for requiring a Type I hood is the capability of the range to produce smoke and grease-laden vapors (e.g. when warming bacon). Provide an approved appeal to the building official acknowledging the range for "warming only" or install a Type I Hood, along with a source of make up air, for the kitchen. Reference Section 507.2.2 IMC 2000.
01/26/2006 PAUL MACHADO ENGINEERING REVIEW Approved
01/28/2006 PETER MCLAUGHLIN ZONING REVIEW Approved Zoning Review may not approve the building plans prior to site plan approval and Structural review approval of building plans.
02/06/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2006 DELMA ROBEY OUT TO CUSTOMER Completed
02/09/2006 SUE REEVES REJECT SHELF Completed