Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL NEW
Permit Number - T05CM04184
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/23/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM04184 8/23/05 1. Provide location of existing panel on site plan. If the location of existing panel is at a separate building or structure, the installation would not meet the requirements of NEC 225 Part II. 2. Specify conduit and conductor size and type. 3. Provide voltage, amperage rating, fault current rating, and number of phases for existing panel. 4. Provide loading information on panel, including existing and new loads. 5. Provide Lighting Power Budget calculations per IECC 2000. |
08/23/2005 | ROBERT SHERRY | WATER | REVIEW | Passed | |
08/23/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/23/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
08/24/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | |
08/26/2005 | JMORALE1 | WWM | REVIEW | Needs Review |