Permit Number: T05CM04184
Parcel: Unknown

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04184
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04184 8/23/05

1. Provide location of existing panel on site plan. If the location of existing panel is at a separate building or structure, the installation would not meet the requirements of NEC 225 Part II.
2. Specify conduit and conductor size and type.
3. Provide voltage, amperage rating, fault current rating, and number of phases for existing panel.
4. Provide loading information on panel, including existing and new loads.
5. Provide Lighting Power Budget calculations per IECC 2000.
08/23/2005 ROBERT SHERRY WATER REVIEW Passed
08/23/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/23/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
08/24/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved
08/26/2005 JMORALE1 WWM REVIEW Needs Review