Permit Number: T05CM04182
Parcel: 13613016C

Review Status: Completed

Review Details: SITE

Permit Number - T05CM04182
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2005 JIM EGAN FIRE REVIEW Approved See comments for building.
08/22/2005 DAN CASTRO ZONING REVIEW Denied COMMENTS: The following comments are based on a building area expansion of less than 25% resulting in full code compliance review of the expansion areas only. All calculations encompass the entire site, whether existing or proposed. Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. The site plan shall include the entire site area including lot dimensions and bearings. On the cover sheet, you may provide a small index drawing of the site showing the area represented on the partial site plan as long as the index drawing provides complete lot dimensions and bearings. (D.S. 2-02.2.1.A.5)

2. On the site plan, label the size (in square feet), maximum height, and use of all existing and proposed buildings and structures including canopies. (D.S. 2-02.2.1.A.6)

3. If proposed modular building is to be reviewed by separate permit, please indicate as so on plan. You may remove all references to proposed modular building or if you choose to show the future modular building, all code requirements shall demonstrate compliance as requested in the following comments.

4. Provide the parking ratio used for the vehicle parking calculation. Vehicle and bicycle parking may not be verified for compliance until this information has been provided. D.S. 2-02.2.1.A.8) (D.S. 2-02.2.2.A.4)

5. Stripe a one-way arrow on the asphalt for the entrance and one for the exit portions of the ingress/egress point and label as so on the plan. The new sign pedestal will be located in the middle of the access point reducing the area required for two-way travel. The pedestal will essentially create a one-way entrance and exit. (D.S. 2-02.2.1.A.11)


6. Per D.S. 3-05.2.2.B.1, a minimum five (5) foot wide pedestrian refuge area shall be provided between the proposed modular building and the PAAL. Within the five (5) foot pedestrian refuge area, a minimum four (4) foot wide accessible concrete sidewalk shall be included. The sidewalk shall connect to the existing on-site pedestrian circulation system.

7. Label and dimension existing and future right-of-way and curb location for Golf Links Road. Per the MS&R Plan, Golf Links is designated as a 200 foot right-of-way. Plan currently shows a 75' ½ right-of-way. (D.S. 2-02.2.1.A.19 and .21)

8. If applicable, all existing and proposed easements must be shown on the plan including width, type, and recording docket and page reference. (D.S. 2-02.2.1.A.20)

9. Remove the "subject to section" referenced under the development designator on sheet A1 as it is incorrect. (D.S. 2-02.2.1.A.31)

10. FAR calculation may not be verified for compliance until all buildings have been labeled with their respective size in square feet. (D.S. 2-02.2.2.A.3)

11. Add the building area percent expansion calculation. (D.S. 2-02.2.2.A.6)

12. Provide the last approved site plan for reference. Additional comments may be forthcoming as a result of any changes to the site not shown on the last approved site plan.

13. As per Federal ADA requirements, all wheel chair ramps shall have the Truncated Domes instead of the standard grooves, which are shown on City of Tucson Standard Detail 207. Aside from the Truncated Domes, the wheel chair ramps shall be constructed in accordance with the Standard Detail 207. Provide a detail of any new accessible parking space, access aisle, and ramp.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608 ext. 1180. An appointment is required to discuss these comments in person.
08/23/2005 DAN CASTRO ZONING HC SITE REVIEW Denied As per Federal ADA requirements, all wheel chair ramps shall have the Truncated Domes instead of the standard grooves, which are shown on City of Tucson Standard Detail 207. Aside from the Truncated Domes, the wheel chair ramps shall be constructed in accordance with the Standard Detail 207. Provide a detail of any new accessible parking space, access aisle, and ramp.
08/25/2005 JOE LINVILLE LANDSCAPE REVIEW Denied 1. Landscaping requirements apply to expansion of existing development as follows: On sites where the gross floor area of the existing building(s) is more than ten thousand (10,000) square feet, expansion in square footage of land area, floor area, lot coverage, or vehicular use area as follows:

If the expansion is less than 25%, the requirements of this Division apply only to the proposed expansion. Existing development on the site is subject to the zoning regulations in effect at the time the existing development received zoning approval per LUC 3.7.1.2.B
If the expansion is 25% or greater or if expansions as of February 15, 1991 cumulatively result in a 25% or greater expansion in land area, floor area, lot coverage, or vehicular use area, the requirements of this Division apply to the entire site per LUC 3.7.1.2.B. It is not clear from the site plan what the existing building square footage is and what percentage expansions are proposed. Provide percent expansion calculations for both building area and vehicle use area. Expansions are cumulative. Additional comments may be necessary once the percentage expansion is calculated on the plan.

2. Provide a copy of the last approved site plan and last approved landscape plan. Additional comments may be necessary once copies of approved plans have been provided.

3. Per DS 2-07.0, the submitted landscape plan must depict the entire site to verify that entire site meets current minimum requirements. Revise to include the whole site and the perimeter lot lines. Include the location, size and name of existing vegetation to remain in place.

4. A street landscape border (see LUC Sec. 3.7.2.4) is a landscape area with a minimum width of ten (10) feet, running the full length of the street property line(s) bounding the site except for points of ingress-egress. On streets designated as Major Streets and Routes (MS&R), the street landscape border is measured from the MS&R right-of-way line as determined by LUC 2.8.3.4. Fifty (50) percent or more of the street landscape border area must have shrubs and vegetative ground cover per LUC 3.7.2.4

5. Indicate square footage of all landscaped areas and calculation of the percentage of vegetative coverage per DS 2-07.2.2.2.g.

6. Submit an NPPO plan or application for exception, including acceptable documentation which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property. Photographs of the site are necessary for NPPO approval per DS 2-15.2.0.C

7. Within a vehicular use area, one (1) canopy tree is required for each 10 motor vehicle parking spaces and every parking space shall be located within forty (40) feet of the trunk of a canopy tree (as measured from the center of the tree trunk) per LUC 3.7.2.3.A.1.a

8. A 10' interior landscape border is required along site boundaries of the adjacent residential properties per LUC Table 3.7.2-I Example of this can be found @ http://www.ci.tucson.az.us/dsd/Codes___Ordinances/DevStd206.pdf 2-06.8 FIGURE 6

9. Along a designated Major Street & Route (MS&R) such as Golf Links Road a 30" continuous screen along the MS&R frontage for screening of vehicle use area, and other uses, must be provided per LUC Table 3.7.2-

10. The MS&R plan shows a right-of-way width for Golf Links Road of 200 feet. Revise plan to show correct MS&R future right-of-way location and show on site plan the future sight visibility triangles per DS 2-02.2.2.1.A.10
08/25/2005 PETER MCLAUGHLIN NPPO REVIEW Denied Submit an NPPO plan or application for exception, including acceptable documentation which clearly indicates that the project will not impact Protected Native Plants. Such documentation includes photographs of the site taken from all sides of the property. Photographs of the site are necessary for NPPO approval per DS 2-15.2.0.C
09/06/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Hudson Design DATE: September 6, 2005
Robert M. Wier
439 N. 6tn Avenue
Tucson, Arizona 85705

SUBJECT: 8900 E. Golf Links Road, New Life Church
Site plan T05CM04182 (First Review)
T14S, R15E, Section 27

RESUBMITTAL REQUIRED: Site Plan and Drainage Report.

The Site Plan (SP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. As per the Federal ADA requirements, all wheel chair ramps shall have the truncated domes instead of the standard grooves that are shown on COT SD 207. Aside from the Truncated Domes, all wheel chair ramps shall be constructed in accordance with COT SD 207.
3. Please provide property description per D.S. 2-02.2.1.3.
4. Please label lot dimensions and bearings per D.S. 2-02.2.1.5
5. Provide all existing and proposed buildings and structures, including location, size, height, overhangs, canopies, and use per D.S. 2-02.2.1.6.
6. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
7. Show all points of egress and ingress including locations and width of driveways and parking area access lanes (P.A.A.L.) per D.S. 2-02.2.1.11.
8. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14.
9. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15.
10. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
11. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
12. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
13. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the SP.
14. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
15. Location and orientation of existing major physical features, such as railroad tracks and drainageways per D.S. 2-02.2.1.22.
16. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
17. Show Site plan number (T05CM04182) on all sheets per D.S. 2-02.2.1.29.
18. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0.
19. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. Please address.
20. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
21. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
22. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
23. List the consulting engineer and the owner/developer on the plans with the pertinent information.
24. A floodplain use permit may be required.
25. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
26. "A grading permit and Stormwater Pollution Prevention Plans (SWPPP's) will be required for this project. Submit 3 sets of grading and SWPPP's with text, upon completion and submittal of a grading permit application. A grading permit may not be issued prior to site plan approval. Subsequent comments may be necessary, depending upon the nature and extent of revisions that occur to the plans".
Drainage Report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. A Drainage report is required for any site greater than one acre in size or for any site subject to detention requirements…..per S.M.D.D.F.M., chap. II, 2.1.2.
3. The content and format of the Drainage Report should follow S.M.D.D.F.M., chap. II, 2.2.
4. Show the project address or administration address on the cover sheet of the DR.
5. If applicable, add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the DR.
If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax C:/8900 E. Golf Links Site

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2006 JMORALE1 OUT TO CUSTOMER Completed
01/11/2006 SUE REEVES REJECT SHELF Completed