Permit Number: T05CM04182
Parcel: 13613016C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04182
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/13/2006 RAUL PALMA BUILDING-COMMERCIAL REVIEW Approved
01/17/2006 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. According to the architect, sheet M3 is not part of the current drawing set. The water calculation note on sheet M4 addresses pipe location but does not consider either pipe sizes or the water pressure available for friction in the existing water system. Show that the new water piping for the drinking fountain and the future portable building will not cause the existing piping to be overloaded. Reference Section 101.5.1, UPC 1994.
01/17/2006 JIM EGAN FIRE REVIEW Approved
01/28/2006 PETER MCLAUGHLIN ZONING REVIEW Denied Zoning Review may not approve the building plans prior to site plan approval and Structural review approval of building plans.
01/30/2006 PAUL MACHADO ENGINEERING REVIEW Approved
02/06/2006 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2006 DELMA ROBEY APPROVAL SHELF Completed
02/09/2006 DELMA ROBEY OUT TO CUSTOMER Completed
02/09/2006 DELMA ROBEY REJECT SHELF Completed