Permit Number: T05CM04182
Parcel: 13613016C

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T05CM04182
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/12/2006 JIM EGAN FIRE REVIEW Approved
01/26/2006 PAUL MACHADO ENGINEERING REVIEW Approved
01/28/2006 PETER MCLAUGHLIN NPPO REVIEW Passed
01/28/2006 PETER MCLAUGHLIN ZONING REVIEW Denied COMMENTS:

1. The following comments are based on a building area expansion of less than 25% resulting in full code compliance review of the expansion areas only. All calculations encompass the entire site, whether existing or proposed. Add a calculation of percentage building calculation (see comment 2 below regarding proposed/existing sheds).
DS 2-02.2.1.A.6

2. The submitted site plan shows existing sheds, which are not shown on the approved site plan. They are shown to be located in an area which was part of the approved gravel parking lot on the original approved site plan. These sheds must meet code requirements for pedestrian circulation and vehicle access to the adjacent parking area. Show pedestrian connections to these sheds on the site plan and dimension surrounding PAALS to demonstrate that they meet the minimum required width for two-way vehiclular access. A minimum 5-foot pedestrian refuge is required between buildings and vehicle use area. Within the five (5) foot pedestrian refuge area, a minimum four (4) foot wide accessible concrete sidewalk shall be included. The sidewalk shall connect to the existing on-site pedestrian circulation system. Revise plan to show the required pedestrian refuge area and pedestrian connections, including that area, as shown on the approved plan, located in between the classroom buildings and the gravel parking lot. Include the sheds, along with the new proposed shed to the north of the sanctuary, as building square footage area for calculations including building area expansion and FAR Indicate the height and dimensions of all sheds/accessory sturctures, including ramadas. FAR calculation may not be verified for compliance until all buildings, including sheds have been labeled with their respective size in square feet. D.S. 2-02.2.2.A.3
DS 2-08.3.1
DS 2-02.2.1.A.12
DS 2-02.2.2.A.6
DS 3-05.2.2.B.1

3. Dimension fully the existing gravel parking lot area as per the approved site plan. This portion of the parking area appears to have been built with a different layout than is shown on the approved site plan. Demonstrate that this parking area meets code for all dimensions (width and length of parking spaces, wheelstop dimensions, PAAL widths, etc.
Parking spaces and PAALs must meet code for dimensions, access and maneuverability.

4. If the future modular building is to be permitted later as indicated by keynote 28, it may be removed from the site plan so that the vehicle use area, parking spaces and required pedestrian circulation may be dimensioned clearly. If you choose to show the future modular building, code compliance for the surrounding parking area shall be demonstrated on the plan.

5. Add a note to the site plan that the project meets the criteria for LUC 2.8.3, MS&R Setback Zone and LUC 2.8.4, Gateway Corridor Zone.

6. As per Federal ADA requirements, all wheel chair ramps shall have the Truncated Domes instead of the standard grooves, which are shown on City of Tucson Standard Detail 207. Aside from the Truncated Domes, the wheel chair ramps shall be constructed in accordance with the Standard Detail 207. Provide a detail of h/c accessible parking space, access aisle, and ramp.

7. There is a dumpster (keynote 25) shown within the approved vehicle use. This dumpster location was not shown on the approved site plan. Revise or demonstrate that the location of the refuse container meets code and does not reduce the adjacent 2-way PAAL width to less than the required 24 feet.
DS 2-02.2.1.A.32

8. Show the adjacent zoning for the entire site on the site plan cover sheet.
DS 2-02.2.1.A.28

If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608 ext. 1178. An appointment is required to discuss these comments in person.
01/28/2006 PETER MCLAUGHLIN ZONING HC SITE REVIEW Denied See zoning review comments.
01/28/2006 PETER MCLAUGHLIN LANDSCAPE REVIEW Denied 1. Keynote 12 indicates an existing dumpster which does not appear on the approved site plan and is located within the area shown as vehicle use area/PAAL on the previously approved site plan. Indicate on a detail how screening requirements are met. Per Table 3.7.2-I, a 6-foot wall is required to screen refuse storage container from adjacent residetially zoned property and a street landscape border is required along Golf Links Road which is a designated MS&R and Gateway Route.
LUC 3.7.2-I

Final Status

Task End Date Reviewer's Name Type of Review Description
02/09/2006 DELMA ROBEY OUT TO CUSTOMER Completed
02/09/2006 SUE REEVES REJECT SHELF Completed