Permit Number: T05CM04177
Parcel: 13322471B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04177
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/10/2005 JMORALE1 FIRE REVIEW Needs Review
08/10/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the size, route, and termination of the T&P relief pipe from the water heater.
2. Provide a riser diagram with pipe sizes for the water supply.
3. Show how the water piping was sized. Reference Section 610.1, UPC 1994.
4. Provide the required minimum plumbing fixtures per Section 2000, IBC 2003, as modified by the City of Tucson.
5. If the water heater is not provided with integral heat traps, provide heat traps and insulation of the first 8' of the hot and cold water piping from the water heater. Reference Section 804, IECC, 2000.
08/10/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1) PROVIDE EXIT SIGNS.
08/10/2005 JMORALE1 WWM REVIEW Needs Review
08/10/2005 HEATHER THRALL ZONING REVIEW Approved
08/10/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide calculations to show the amount of outside air that is to be provided to the space. Reference Section 403.3, IMC 2000.
08/10/2005 JMORALE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/10/2005 ROBERT SHERRY WATER REVIEW Approved
08/10/2005 BLANCA ESPINO ENGINEERING REVIEW Approved