Review Details: COMMERCIAL TI
Permit Number - T05CM04177
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/10/2005 | JMORALE1 | FIRE | REVIEW | Needs Review | |
| 08/10/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the size, route, and termination of the T&P relief pipe from the water heater. 2. Provide a riser diagram with pipe sizes for the water supply. 3. Show how the water piping was sized. Reference Section 610.1, UPC 1994. 4. Provide the required minimum plumbing fixtures per Section 2000, IBC 2003, as modified by the City of Tucson. 5. If the water heater is not provided with integral heat traps, provide heat traps and insulation of the first 8' of the hot and cold water piping from the water heater. Reference Section 804, IECC, 2000. |
| 08/10/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Approved | 1) PROVIDE EXIT SIGNS. |
| 08/10/2005 | JMORALE1 | WWM | REVIEW | Needs Review | |
| 08/10/2005 | HEATHER THRALL | ZONING | REVIEW | Approved | |
| 08/10/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide calculations to show the amount of outside air that is to be provided to the space. Reference Section 403.3, IMC 2000. |
| 08/10/2005 | JMORALE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 08/10/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/10/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved |