Permit Number: T05CM04167
Parcel: 125076370

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04167
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04167 8/12/05

1. Load calculations for Section 3 rely on NEC 220.36, which may only pertain to feeder and service loads for new restaurants. Since this is not a new restaurant, such methodology may not be used in its present form. It appears that Section 3 is overloaded.
08/12/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Termination of a secondary drain over a ceiling tile is not "conspicuous".
08/12/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/16/2005 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review