Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T05CM04167
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/12/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/12/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM04167 8/12/05 1. Load calculations for Section 3 rely on NEC 220.36, which may only pertain to feeder and service loads for new restaurants. Since this is not a new restaurant, such methodology may not be used in its present form. It appears that Section 3 is overloaded. |
| 08/12/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Termination of a secondary drain over a ceiling tile is not "conspicuous". |
| 08/16/2005 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review |