Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2005 JIM EGAN FIRE REVIEW Approved
08/09/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show the route and termination of the T&P relief pipe from the water heater.
2. Clarify how (or if) RP-1 in the plumbing fixture specifications is related to this project.
08/09/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Needs Review
08/09/2005 ROBERT SHERRY WATER REVIEW Approved
08/09/2005 DAVID RIVERA ZONING REVIEW Approved
08/09/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the termination point of the secondary condensate drains.
2. Revise the outside air quantities for the fan coils per Section 403.3.2, IMC 2000.
08/09/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/09/2005 LOREN MAKUS ENGINEERING REVIEW Approved
08/12/2005 GERRY KOZIOL WWM REVIEW Approved