Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04167
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/09/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
08/09/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show the route and termination of the T&P relief pipe from the water heater. 2. Clarify how (or if) RP-1 in the plumbing fixture specifications is related to this project. |
08/09/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
08/09/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/09/2005 | DAVID RIVERA | ZONING | REVIEW | Approved | |
08/09/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the termination point of the secondary condensate drains. 2. Revise the outside air quantities for the fan coils per Section 403.3.2, IMC 2000. |
08/09/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
08/09/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
08/12/2005 | GERRY KOZIOL | WWM | REVIEW | Approved |