Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T05CM04166
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/09/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T05CM04166 8/9/05 1. Minimum font size is 1/8". Enlarge as necessary. 2. On Ckt 4, note that show window receptacles shall be counted as 200 VA/LF. Reference NEC 220.3 (B) (7). 3. For better feeder load calculations, please verify that existing RTU VA count includes 25% for the largest motor, and add 25% to the count as appropriate for the continuous loading on circuits 7 and 9. |
08/09/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
08/09/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/09/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/10/2005 | JIM EGAN | FIRE | REVIEW | Denied | Need Site/Location plan. |
08/26/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
08/26/2005 | CAGUILA1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
08/26/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review | |
08/26/2005 | CAGUILA1 | ENGINEERING | REVIEW | Needs Review |