Permit Number: T05CM04166
Parcel: 12904158D

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04166
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04166 8/9/05

1. Minimum font size is 1/8". Enlarge as necessary.
2. On Ckt 4, note that show window receptacles shall be counted as 200 VA/LF. Reference NEC 220.3 (B) (7).
3. For better feeder load calculations, please verify that existing RTU VA count includes 25% for the largest motor, and add 25% to the count as appropriate for the continuous loading on circuits 7 and 9.
08/09/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/09/2005 ROBERT SHERRY WATER REVIEW Approved
08/09/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/10/2005 JIM EGAN FIRE REVIEW Denied Need Site/Location plan.
08/26/2005 CAGUILA1 WWM REVIEW Needs Review
08/26/2005 CAGUILA1 BUILDING-COMMERCIAL REVIEW Needs Review
08/26/2005 CAGUILA1 ZONING REVIEW Needs Review
08/26/2005 CAGUILA1 ENGINEERING REVIEW Needs Review