Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04114
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2005 JIM EGAN FIRE REVIEW Approved
08/05/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
08/05/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) ONE WOMEN'S RESTROOM, ONE MEN' RESTROOM BOTH ACCESSIBLE ARE REQUIRED. pROVIDE SITE PLAN SHOWING DISTANCE TRAVELED TO ACCESSIBLE RESTROOMS.
08/05/2005 ROBERT SHERRY WATER REVIEW Approved
08/05/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
08/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the amount of outside air for the rooftop A/C units to at least the minimum outside air called for in the calculations.
2. Relocate the condensate drain that is currently draining to a plumbing vent.
08/05/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/09/2005 CAGUILA1 WWM REVIEW Needs Review
08/09/2005 CAGUILA1 ZONING REVIEW Needs Review