Review Details: COMMERCIAL TI
Permit Number - T05CM04114
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 08/05/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 08/05/2005 | CHRISTY FOREMAN | BUILDING-COMMERCIAL | REVIEW | Denied | 1) ONE WOMEN'S RESTROOM, ONE MEN' RESTROOM BOTH ACCESSIBLE ARE REQUIRED. pROVIDE SITE PLAN SHOWING DISTANCE TRAVELED TO ACCESSIBLE RESTROOMS. |
| 08/05/2005 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 08/05/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Approved | |
| 08/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the amount of outside air for the rooftop A/C units to at least the minimum outside air called for in the calculations. 2. Relocate the condensate drain that is currently draining to a plumbing vent. |
| 08/05/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 08/09/2005 | CAGUILA1 | WWM | REVIEW | Needs Review | |
| 08/09/2005 | CAGUILA1 | ZONING | REVIEW | Needs Review |