Permit Number: T05CM04111
Parcel: 10820011F

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM04111
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how the condensate from the coolers is being handled.
2. Clarify the notes regarding the "water pipe from wall".
08/12/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T05CM04111 8/5/05

1. On the electrical plan, please correct the location of the rooftop receptacles to Ckt R-28, not R-21.
2. The load on R-8, 10, 12, reference Keynote 13, appears high for 15 MCA.
3. In the General Notes Sheet E-2, correct 1999 NEC to 2002.
4. Please note that the "c" value for 4/0 in metallic conduit is aprox. 15082, not 7992. This may be academic due to the 65/10K series rating of the new panel, but the Engineer of Record may desire to provide the correct figures for the record.