| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/05/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Show how the condensate from the coolers is being handled. 2. Clarify the notes regarding the "water pipe from wall". |
| 08/12/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T05CM04111 8/5/05 1. On the electrical plan, please correct the location of the rooftop receptacles to Ckt R-28, not R-21. 2. The load on R-8, 10, 12, reference Keynote 13, appears high for 15 MCA. 3. In the General Notes Sheet E-2, correct 1999 NEC to 2002. 4. Please note that the "c" value for 4/0 in metallic conduit is aprox. 15082, not 7992. This may be academic due to the 65/10K series rating of the new panel, but the Engineer of Record may desire to provide the correct figures for the record. |