Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T05CM04097
Parcel: 12710017D

Review Status: Completed

Review Details: OTHER

Permit Number - T05CM04097
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/22/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Add HP C4-C to Circuit C-19,21,23 on Panel Schedule.
2. CB 70/3 Ckt C-19,21,23 is offset one space on Panel Schedule.
3. One of the A/C units on Building B needs to be re-labeled as "B2-C". B4-A is used twice.
4. It appears that Keynote 9 is used inappropriately on Building D in a few places. Conduit is marked as J-Box. I believe Keynote 7 fits the intent.
5. HP D3-A is used twice on Bldg D.
6. Three of the A/C units on Bldg D do not have a connection to any circuit, on Electrical Plan Building D.
7. HP D8-A is shown on Bldg D. No such HP this project.
8. Please mark Building E as such on the plan view layout.
9. Check correspondence between A/C Equipment Schedule and field installation per building plans. B2-C and D1-8 are on the Schedule but not the plans. D3-8 is on the plans but not the schedule.
10. The disconnect on Building A appears to violate the requirements of NEC 225.30.
11. New Panel AC Building B appears to violate the requirements of NEC 225.30.
12. The disconnect on Building D appears to violate the requirements of NEC 225.30.
13. The disconnect on Building A appears to violate the requirements of NEC 225.30.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/23/2005 SUE REEVES REJECT SHELF Completed