Permit Number: T05CM04096
Parcel: 12710017D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05CM04096
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/20/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Add HP C4-C to Circuit C-19,21,23 on Panel Schedule.
2. HP D3-A is used twice on Bldg D. Coordinating with Mechanical, it appears that the first unit on the left should be HP D8-A. Note that D8-A appears on the Mechanical Equipment Schedule, Sheet M-2, but not on the A/C Equipment Schedule, Sheet E-4.
3. HP D8-A is shown on Bldg D. No such HP this project. This comment was made on the first submittal, however if one inspects the Mechanical, it is on there. This relates to Comment #9 of the first submittal.
4. The disconnect on Building A appears to violate the requirements of NEC 225.30. See Comment #9 below.
5. New Panel AC Building B appears to violate the requirements of NEC 225.30. See Comment #9 below.
6. The disconnect on Building D appears to violate the requirements of NEC 225.30. See Comment #9 below.
7. The disconnect on Building E appears to violate the requirements of NEC 225.30. See Comment #9 below.
8. The note added on Sheet E-3 does not document to this jurisdiction that the facility is under "…single management where documented safe switching procedures are established and maintained for disconnection." Reference NEC 225.30 (E). A hospital or university complex would fit this description in our view. If you care to evoke this Code Section this will be a matter which we should discuss.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/24/2005 JMORALE1 OUT TO CUSTOMER Completed
10/24/2005 JMORALE1 REJECT SHELF Completed