Permit Number: T05CM04082
Parcel: 11616170B

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T05CM04082
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/03/2005 BLANCA ESPINO ENGINEERING REVIEW Needs Review
08/04/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Passed
08/04/2005 JIM EGAN FIRE REVIEW Passed
09/22/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/22/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Needs Review T05CM04082 8/4/05

1. Provide Electrical Plans designed and sealed by an Electrical Engineer, registered in the State of Arizona. See the attached list of Electrical Permit Requirements.
2. It appears that this site is a candidate for classification as a Class I Division 2 area per NEC 500. Electrical Engineer shall evaluate such parameters and outline such area of classification on plans.
3. Missing items include but are not limited to power requirements of electrical loads, panel and circuit designations for electrical loads, conduit and conductor size and type, electrical disconnects, panel schedules, load calculations, single line diagram, grounding electrode system, and fault calculations.
09/22/2005 HEATHER THRALL ZONING REVIEW Approved
09/22/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
09/22/2005 ROBERT SHERRY WATER REVIEW Passed
09/22/2005 GERRY KOZIOL WWM REVIEW Passed