Permit Number - T05CM04030
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Stopped
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/03/2005 | ANY | BUILDING-COMMERCIAL | REVIEW | Stopped | |
| 08/03/2005 | ANY | ELECTRICAL-COMMERCIAL | REVIEW | Stopped | t05cm04030 8/3/05 1. Identify panel and circuit number for the sign circuit. 2. Provide the required disconnect per NEC 600.6. 3. Provide panel location on site plan. 4. Specify conduit and conductor size and type. 5. Specify overcurrent protective device site. 6. Provide documentation of listing. 7. Provide more information on the transformer, electrical specifications. |