Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T05CM04023
Parcel: 110055410

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04023
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2005 JIM EGAN FIRE REVIEW Approved
08/02/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the vent sizes to comply with the requirements of Section 904.1, UPC 1994.
08/02/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Approved 1) PROVIDE CODE ANALYSIS EXISTING SQ. FOOTAGE OF BUILDING IS UNDER THE ALLOWABLE. CLARIFY MOST RESTRICTIVE USE OF BUILDING.
2) PROVIDE CLEAR FLOOR SPACE ENVELOPES FOR EACH FIXTURE.
3) PROVIDE STANDARD WALL SECTION FOR INTERIOR PARTITIONS.
4) PROVIDE ACCESSIBILITY FROM LOBBY INTO OFFICE SPACE. CLEARANCE FOR DOOR.
08/02/2005 ROBERT SHERRY WATER REVIEW Approved
08/02/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved
08/02/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show how recirculation of the air from the restrooms will be prevented. Reference footnote b, Table 403.3, IMC 2000.
2. Show that the building structure is adequate to support the new heat pump.
08/03/2005 MICHAEL ST. PAUL ZONING REVIEW Approved
08/03/2005 CAGUILA1 WWM REVIEW Approved
08/03/2005 PATRICIA GILBERT ENGINEERING REVIEW Approved