Permit Number: T05CM04021
Parcel: 141153540

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05CM04021
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2005 ROBERT SHERRY WATER REVIEW Approved
08/02/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied T05CM04021 8/2/05

1. Minimum font size is 1/8". Please enlarge as necessary.
2. Please re-evaluate the 360 VA on the barber chair receptacles. Verify that the equipment intended for these circuits will not draw any more load.
3. For better accuracy, please add 25% of the largest motor on Panel P7.
4. Provide Lighting Power Budget Calculations per the 2000 IECC.
08/02/2005 HEATHER THRALL ZONING REVIEW Approved
08/02/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/02/2005 JIM EGAN FIRE REVIEW Approved
08/02/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a riser diagram for the water service.
2. Show the route and termination of the T&P relief. Termination at an elevated janitor's sink is not allowed.
3. Show how the water heater is to be supported and show the installed height.
08/02/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Provide restroom facilities per the design work stations or modify work stations for on e restroom facility.
2) clarifyu restroom meets ANSI 2003 standards A117.1.
3) Clearance or accessibilty to restroom past the work stations.
08/02/2005 BLANCA ESPINO ENGINEERING REVIEW Approved
09/23/2005 DROBEY1 WWM REVIEW Needs Review